UPS runtime estimator
Enter the numbers from your UPS datasheet and your own load reading. You get an estimate of how long the battery could carry that load, and a VA to watts conversion. Nothing is filled in for you, and no product data is stored on this page.
The formulas
runtime in hours = battery watt-hours × (inverter efficiency ÷ 100) ÷ load in watts, then × 60 for minutes.watts = volt-amperes × power factorwatt-hours = battery volts × amp-hours × number of batteries, for identical batteries.
What the estimate assumes
- This estimate assumes the UPS can support your load. Check the unit's watt and VA ratings first: a load above the rating still gives a number here, but the unit may not carry it.
- The load stays at the watts you entered for the whole outage.
- All of the battery's nominal watt-hours can be used (a usable depth of 100%). A real UPS stops before the battery is empty, so less energy is available. This is an idealised estimate.
- Efficiency is one fixed percentage. Use the battery-mode inverter efficiency at your load if the datasheet lists it. In a real unit it changes with the load.
- When you work out watt-hours from volts and amp-hours, use the nominal voltage per battery.
- Batteries give less energy as they age, when it is cold, and when they are discharged quickly. Real runtime depends on battery age and discharge rate, so it can be shorter than this estimate.
- The numbers come from the unit's own datasheet. The manufacturer's runtime chart for the exact model, at your load, is the figure to trust.
Sources and where to read more
- How to Size a UPS for a NAS and Homelab (VA, Watts, Runtime), on this site: adding up watts and VA, and reading a runtime chart.
- The difference between VA and Watts, Eaton: watts = VA × power factor, with a power factor from 0 to 1.
- UPS sizing guide, Eaton: runtime depends on the load, so size a UPS by load and runtime.
- UPS Battery Backup Calculator: Runtime & Battery Size, BLUETTI: the energy equations (watt-hours from nominal volts and amp-hours, and runtime from watt-hours, efficiency and load). That calculator also applies a usable-depth factor, which this page sets to 100%.
- NIST Guide to the SI, Chapter 5: Units Outside the SI, NIST: 1 hour = 60 minutes.
- NIST Guide to the SI, Chapter 7: Rules and Style Conventions for Expressing Values of Quantities, NIST: 1 percent = 0.01.